500kw 625kva Perkins diesel generator dg set for AC power station
Prime 500kw 625kva Perkins diesel generator dg set for AC power station, powered by 6 cylinders 4 stroke turbo charged UK Perkins 2806A-E18TAG2 diesel engine, Stamford HCI544FS self-excited alternator or Marathon, Leroy Somer, Mecc alternator; Deepsea, ComAp, Smartgen control panel is available for intelligent control, suitable for continuously running in diesel power station in South Africa, Dubai, Russia, Pakistan, India etc.
General Details
500kw 625kva Perkins diesel generator dg set for AC power station overall specifications
Model: | 500GF-P |
Prime Power: | 500KW/625KVA |
Standby Power: | 550KW/690KVA |
Diesel Engine Specifications
Engine Model | 2806A-E18TAG2 |
Engine Manufacturer | Perkins UK |
Cylinder quantity | 6 |
Cylinder Arrangement | In-line |
Cycle | 4 |
Aspiration | Turbo charged |
Bore x Stroke (mm x mm) | 145×183 |
Displacement | 18.13 L |
Compression Ratio | 14.5:1 |
Prime power / Speed (KW/RPM) | 584kw/1500 |
Standby power/ Speed (KW/RPM) | 628kw/1500 |
Governor type | Electronic |
Piston Speed | 9 m/s |
Typical genset electrical output | 520 kw |
Total Lubrication System Capacity (L) | 62 |
Total Coolant Capacity (L) | 61 |
Fuel Consumption at 100% load (L/hour) | 132 L |
Starter motor | 24V |
Alternator | 24V |
Minimum cranking speed | 115 rpm |
Alternator Specifications
Alternator model | HCI544FS |
Alternator manufacturer | STAMFORD |
Exciter type | Single bearing, Brushless, Self-excited |
Rated output prime power | 670KVA |
Rated speed | 1500 rpm |
Rated frequency | 50Hz |
Number of phase | 3 |
Rated voltage | 400V (Available with custom requirements) |
Power factor | 0.8 |
Voltage regulation NL-FL | ≤±1% |
Insulation grade | H |
Protection grade | IP23 |
Dimension & Weight
Open Type Overall Size:L×W×H (mm) | 4700×1900×2500 | Silent Type Overall Size:L×W×H (mm) | 5250×2600×3500 |
Open Type Weight (kg) | 4300 | Silent Type Weight (kg) | 5800 |
Inquire this product
Product Video