1. 250kw Cummins Natural Gas Generator Set Overall Technical Specifications:

Genset Model 250GT-CT
Rated Power 250KW / 312.5KVA
Rated Speed/ Rated Frequency 1500 rpm /50Hz
Rated Voltage 400/230V
Power Factor 0.8
Phase/Wire 3Phase/4Wire
Rated current (A) 468
Gas Type natural gas
Overall Size (mm) 3800x1550x2000
Weight (kg) 3850
Engine Model Cummins KTAA19
Air intake way Turbo intercooled
Cooling way Closed cooling cycle
Cylinder 6
Displacement (L) 19
Bore×Stroke (mm) 159×159
Max. standby power @50Hz 280kw / 350kva
Alternator Model STAMFORD HCI444ES
Rated Power 260kw / 325kva
Excitation way Brushless and self exciting
AVR MX321
Insulation class H
Protection IP23
Remarks:

1.  Fuel requirements :methane content≥92% ( or Gas low heat value ≥ 33 MJ/Nm3 ), sulfur content≤200PPM,  impurities size≤5μm, impurities content≤50mg/Nm³, water content≤40 g/Nm3 ;

2.  Manufacturing standards:ISO8528-5,GB/T2820.5-2009,GB/T22343-2008;

3.  Every gas genset have been pass the test under the load of 0%,25%,50%,75%,100% and the response ability of static, dynamic test, all the protection device and control system are pass strict inspection before they leave factory.

2. Optional parts for 250kw Cummins Natural Gas Generator

1). Soundproof canopy
2). Parallel cabinet
3). Synchronization cabinet
4). ATS
5). Inlet gas pressure adjusting valve
6). Gas water separator
7). Extra spare parts

3.Warranty Policy for 250kw Cummins Natural Gas Generator

1)Since gen-set reached the agreed destination, its main parts will be guaranteed within 12 months or 1000 hours (subject to the earlier mature term).
2)We take charge of all troubles caused by gen-set’s fault and repair according to the regulation stipulated by original plants.
3)Factors not accordance with the regulation of original plants such as fragile parts, daily consumed components, wrong operating, lack of maintenance are not include in the quality guarantee.

4. Declaration of 250kw Cummins Natural Gas Generator

The 250kw cummins natural gas generator set designed according to environment condition set by ISO 3046:atmospheric pressure 100 kPa, sea level height 110m inlet gas temperature 25℃, relative humidity 30% and reference gross heat value of natural gas at minimum 33MJ/NM3(>=92% CH4 ).While using in places which don’t meet these conditions, generator rated power and outlet gas temperature parameters will be different more or less.

Feature parameters and technical data provided above was calculated through program with massive natural gas experiments and actual use data based on environment condition and natural gas heat value and content mentioned above.

All generator parameters of 250GF-CT 250kw cummins natural gas generator set such as output power, heat consumption were rated value under basic load ( 100% load ) . Detailed analysis report of 250kw cummins natural gas generator 250GF-CT in different conditions will be provided by our engineer according to user’s actual environments and gas composition conditions if needed.

Other party are not allowed to use our technical parameters for research and business purpose without our permission. We reserved the rights of changing our design without notify customer or the third party.

Inquire this product

    Product Video