48kw 60kva Perkins small diesel generator open type and silent type

48kw 60kva Perkins small diesel generator open type and silent type, powered by UK Perkins 3 cylinders 4 cycles 1103A-33TG2 diesel engine and Stamford UCI224E 3 phases 4 wires alternator, same quality as FG Wilson diesel generator but much cheaper price, they are ideal as prime or backup usage if electricity outage in villa, park, hospital, shopping mall, bank etc. Either 50Hz 1500rpm 230V / 400V or 60Hz 1800rpm 110v / 440v - 480v output are available in Vander, send us inquiry today to get a discount price.

SKU: 48GF-P Category:
General Details

48kw 60kva Perkins small diesel generator open type and silent type overall specifications

Model: 48GF-P
Prime Power: 48KW/60KVA
Standby Power: 52KW/65KVA

Diesel Engine Specifications

Engine Model 1103A-33TG2
Engine Manufacturer Perkins UK
Cylinder quantity 3
Cylinder Arrangement In-line
Cycle 4
Aspiration Turbo charged
Bore x Stroke (mm x mm) 105×127
Displacement 3.3 L
Compression Ratio 17.25:1
Prime power / Speed (KW/RPM) 55kw/1500
Standby power/ Speed (KW/RPM) 60.5kw/1500
Governor type Electric
Piston Speed 6.35m/s
Typical genset electrical output (0.8 pf?25°C) 48kw
Total Lubrication System Capacity (L) 8.3
Coolant Capacity (L) 4.4
Fuel Consumption at 100% load (L/hour) 13.9 at 1500rpm
Starter motor 12V
Alternator 12V
Minimum cranking speed 105rpm

Alternator Specifications

Alternator model UCI224E
Alternator manufacturer STAMFORD
Exciter type Single bearing, Brushless, Self-excited
Rated output prime power 60KVA
Rated speed 1500 rpm
Rated frequency 50Hz
Number of phase 3
Rated voltage 400V (Available with custom requirements)
Power factor 0.8
Voltage regulation NL-FL ≤±1%
Insulation grade H
Protection grade IP23

Dimension & Weight

Open Type Overall Size:L×W×H (mm) 1600×1300×730 Silent Type Overall Size:L×W×H (mm) 2500×1600×1800
Open Type Weight (kg) 750 Silent Type Weight (kg) 1000
Inquire this product

    Product Video